Fine filtration with a large media area
A pocket filter, also called a bag filter, folds a large area of filter media into a set of pockets held in a frame. The large area keeps pressure drop low and gives the filter a long life for its class. Pocket filters are the usual fine-filtration stage in air handling units, downstream of a coarse pre-filter and, in clean areas, upstream of HEPA filters.
AirMax pocket filters are supplied in the EN 779:2012 classes M5, M6, F7, F8 and F9. Sizes and classes are selected to your housings and airflow.
The EN 779 classes
EN 779:2012 rated medium (M) and fine (F) filters by their average efficiency against 0.4 µm particles in a laboratory test. The standard’s bands are:
| Class | Average efficiency, 0.4 µm (EN 779:2012) |
|---|---|
| M5 | 40 % to below 60 % |
| M6 | 60 % to below 80 % |
| F7 | 80 % to below 90 % |
| F8 | 90 % to below 95 % |
| F9 | 95 % and above |
F7 to F9 filters also had to meet a minimum efficiency requirement. Older documents may use F5 and F6, which were EN 779:2002 class names. Product-specific efficiencies are on the AirMax datasheet for each filter.
Where it fits
- Fine filtration in AHUs serving production, packing and office areas.
- Pre-filtration ahead of HEPA filters, where it extends HEPA life.
- Supply air to paint booths and processes sensitive to dust.
Selection notes
- Choose the class from the job. Comfort ventilation, food areas and HEPA pre-filtration need different classes.
- Size for the airflow. Running a filter above its rated airflow raises pressure drop and lowers efficiency.
- Seal the frame. A gap around the frame lets air bypass the filter entirely.
- Change on pressure drop. A gauge across the bank shows when the recommended final pressure drop is reached. Dusty Cambodian sites may reach it sooner, and a good pre-filter stage slows that down.
- Humidity. Media and frames should suit humid air, and wet filters should not be left in service.
What Nexus provides
As technology partner and authorised distributor for AirMax, we match filters to your housings, advise ISO 16890 equivalents, supply on a planned schedule and can change them under a maintenance contract.