Clean air, the right direction of flow, stable conditions
A clean room in Cambodia does three jobs at once. It keeps airborne particles below a defined limit, classified under ISO 14644-1. It makes air flow from cleaner spaces to less clean ones, using a pressure cascade, so contamination cannot drift in through doors and gaps. And it holds temperature and humidity stable against a hot, humid climate.
HEPA-filtered supply air, enough air changes or unidirectional flow, sealed construction and disciplined operation make that happen. Positive pressure protects the product or patient inside. Negative pressure protects the people outside from what is inside. This article covers the basics for pharmaceutical plants, hospitals and laboratories. It belongs to our industrial air quality guide.
What a cleanliness class means
ISO 14644-1:2015 sets nine classes, ISO Class 1 (cleanest) to ISO Class 9, defined by the maximum number of particles of given sizes per cubic metre of air. As one reference point, ISO Class 5 allows no more than 3,520 particles of 0.5 µm and larger per cubic metre.
Pharmaceutical manufacturing adds its own layer. EU GMP Annex 1, revised in 2022, uses Grades A to D for sterile manufacturing and relates them to ISO classes in two states: “at rest” and “in operation”. Hospitals and laboratories follow their own guidance, typically national health-facility standards or international references, which set requirements by room type rather than by ISO class alone.
How clean rooms are kept clean
Filtration
Supply air passes through a staged filter train that ends in HEPA filters, usually H13 or H14 under EN 1822, mounted in sealed housings in the ceiling. Pre-filters protect them, so the HEPA stage loads slowly and keeps its rated airflow for longer. The housings and their seals matter as much as the media. Installed filters are leak-tested in place, using methods described in ISO 14644-3, both at handover and at intervals afterwards. Our article on air filter classes explains the ratings.
Airflow pattern
Most clean rooms use non-unidirectional (turbulent) flow: clean air enters from ceiling filters, mixes and dilutes particles, and leaves through low-level returns. The most critical zones, such as aseptic filling, use unidirectional flow, often called laminar flow: a steady sheet of filtered air sweeps the work zone in one direction.
Pressure cascade
Rooms are held at stepped pressures, highest in the cleanest space and lower as you move outwards. Air leaks outwards through every door gap and seam, carrying particles away from the critical zone. EU GMP Annex 1 gives a guidance value of at least 10 Pa between adjacent rooms of different grades.
Transfer and entry
Airlocks for people and materials, gowning rooms and pass boxes let things move between grades without collapsing the cascade. Doors are interlocked so both sides of an airlock cannot open together. Gowning procedures, cleaning regimes and how people move through the suite matter as much as the hardware, because people are usually the largest source of particles in an occupied clean room.
Air changes and recovery
In non-unidirectional rooms, cleanliness comes from dilution. The supply airflow, often expressed as air changes per hour, must be high enough to remove the particles that people and processes generate and to carry away heat. The right rate depends on the class, the activity, the heat load and the room layout, so it should be calculated rather than copied from another project. ISO 14644-3 describes test methods, including a recovery test that measures how quickly a room returns to its clean state after a particle challenge.
Positive or negative: who is being protected
| Application | Pressure relative to surroundings | Protects |
|---|---|---|
| Sterile and aseptic manufacturing | Positive | Product |
| Operating theatres | Positive | Patient |
| Protective isolation (immunocompromised patients) | Positive | Patient |
| Airborne infection isolation rooms | Negative | Staff and other patients |
| Potent compound and some laboratory work | Negative, or positive with a negative sink or airlock | Operators and environment |
The US Centers for Disease Control and Prevention’s guidelines for environmental infection control in health-care facilities use a pressure differential greater than 2.5 Pa (0.01 inch water gauge) as the criterion for airborne infection isolation rooms, held negative to the corridor. Where both product and operator protection are needed, designers use airlocks held at an intermediate pressure, called bubbles or sinks, to separate the two.
Positive pressure keeps contamination out. Negative pressure keeps hazards in. Most clean suites need both, in the right order.
The tropical challenge: humidity and heat
In a temperate climate, a clean room HVAC system mostly fights internal heat. In Cambodia it also fights the outdoor air. Fresh air for occupants and pressurisation arrives hot and close to saturation for much of the year. The AHU has to remove that moisture before it reaches the room.
That usually means cooling coils that run cold enough to condense water out of the air, followed by controlled reheat, or a desiccant rotor dehumidifier where very low humidity is needed. Chilled water comes from the central cooling plant, and dehumidifiers from our dehumidifiers range. Our article on humidity control in pharmaceutical and food production goes deeper on setting the humidity target.
Two more local factors deserve attention:
- Power interruptions. If supply fans stop, pressurisation collapses. Decide which fans need backup power, how the system restarts and what alarms the operators see.
- Fabric and seals. Heat and humidity age gaskets and sealants. Room integrity and filter leak tests should be repeated on a schedule, not only at handover.
Why rooms lose their pressure
Pressure cascades rarely fail in one dramatic event. They drift. The most common causes are:
- Filter loading. As supply filters load, supply airflow falls unless the fan control compensates, and room pressure follows.
- Doors. A door propped open, a failed closer or an interlock that has been bypassed.
- Changes nobody coordinated. A new extract point, a fume cupboard or process exhaust added without rebalancing the room.
- Leaky construction. Unsealed service penetrations, light fittings and ceiling panels.
- Blocked returns. Equipment or stored materials pushed against low-level return grilles.
Continuous differential pressure monitoring with alarms catches these early. ISO 14644-2 sets out how to plan monitoring that shows a clean room keeps performing between formal classifications. Logged data also gives quality teams the evidence auditors ask for.
What to settle before design
- The process or clinical activity in each room and what must be protected
- The governing standard: ISO 14644-1 class, GMP grade or health-facility guideline
- Occupancy state for compliance: at rest, in operation or both
- Pressure cascade and the direction of flow between every pair of rooms
- Temperature and relative humidity targets and their tolerances
- People and material flows, airlocks and pass boxes
- Monitoring: differential pressure, particle counts, temperature and humidity, with alarms
- Qualification and validation documents the regulator or auditor expects
The system selector gives a first view of the equipment involved. For sector requirements, see our pharmaceutical and healthcare industry page.
From room data sheet to validated room
A good clean room starts with a room data sheet for every space and ends with test records that prove each room meets it. Between the two sit air handling, filtration, controls and monitoring that must work as one system. We supply HEPA filters, laminar flow units and pass boxes from our air quality and emissions range, with the chilled water and dehumidification behind them, and we commission the whole cascade together.