Positive pressure (room)

Keeping a room at a slightly higher air pressure than its surroundings by supplying more filtered air than is extracted, so air leaks outwards and contaminants stay out.

Positive pressure is a simple principle: if a clean room is at a higher pressure than the corridor, air flows out through door gaps and openings, not in. In a sequence of rooms the cleanest is held highest, forming a pressure cascade. For pharmaceutical cleanrooms, EU GMP Annex 1 (2022) gives a guidance value of 10-15 Pa between adjacent rooms of different grades.

It is used in cleanrooms, packing and filling areas, laboratories and control rooms. Rooms holding hazardous materials or isolation wards do the opposite and are held at negative pressure.

The AHU sets the supply-extract balance; doors, leaky walls and badly placed returns undo it. Fit room differential pressure gauges or sensors with alarms, interlock doors where the design needs it, and recheck the balance after any change to ductwork or filters.

Next step

Need this applied to your plant?