An AHU draws in return and fresh air, filters it, cools or heats it with water or refrigerant coils, and supplies it through ducts. Depending on duty it may add humidification, dehumidification, heat recovery and final filtration up to HEPA for cleanrooms.
In a factory the AHU decides temperature, humidity, air change rate, filtration and room pressure. In a humid climate its cooling coil often does as much work removing moisture as lowering temperature, and coil selection should reflect that latent load.
Specify filters by ISO 16890 class, choose fans and motors for efficiency at the actual operating point, and make coils and drain pans easy to clean. A blocked drain pan or dirty coil in tropical conditions quickly becomes a hygiene and capacity problem.