Chilled water without a cooling tower
An air-cooled chiller produces chilled water for process or comfort cooling and rejects the heat directly to outdoor air through fans and finned coils. There is no cooling tower, no condenser water pumps and no tower water treatment. That makes it the simpler choice for small and medium loads and for sites with limited water or space.
The Nexus range includes air-cooled chillers with scroll compressors for smaller duties and screw compressors for larger ones. Capacities are selected to your load. Ask for a datasheet.
How it works
A refrigeration circuit absorbs heat from the chilled water in the evaporator. Compressors raise the refrigerant pressure and temperature, and the hot refrigerant gas condenses in air-cooled coils, giving up its heat to outdoor air driven by the condenser fans. The condensed refrigerant returns to the evaporator through an expansion device. Multiple compressors or circuits let the chiller match part load and keep some cooling running if one circuit stops.
Where it fits
- Process cooling for plastics, food, beverage and printing.
- Chilled water for AHUs and fan coil units.
- Sites without water for a cooling tower, or without plant-room space.
For large, steady loads, compare a water-cooled screw chiller.
Selection notes
- Select at real ambient. Capacity and efficiency fall as outdoor temperature rises. Select at the design ambient for your site, not at a milder rating condition.
- Clearances. Hot air from the condenser fans must not recirculate to the coil inlets. Space around and above the chiller, and between chillers, matters.
- Part-load performance. Most chillers spend most hours at part load. Compare EER and COP at your typical operating points.
- Coil protection. Dust, pollen and coastal air foul or corrode coils. Coatings and a cleaning routine protect capacity.
- Redundancy. For critical processes, plan N+1 chillers or circuits.
What Nexus provides
Load calculation, chiller selection at site conditions, chilled-water system design, installation and commissioning, and planned maintenance: coil cleaning, refrigerant checks, controls and spare parts. See our chiller maintenance checklist for hot climates.