Relative humidity is the ratio of the actual water vapour pressure in air to the saturation vapour pressure at that temperature, given as a percentage. At 100% RH air is saturated and any further cooling causes condensation.
RH drives most of the moisture damage seen in plants: mould on stored fabric and cartons, caking powders, corrosion, static and dimensional change in paper and textiles. Many processes and stores are specified in RH, so it is what operators watch.
Practical note: RH changes with temperature even when the moisture content stays the same. Warming air lowers its RH; cooling it raises it. A store that reads acceptable in the afternoon can reach saturation at night. For design, work in dew point or moisture content, then check the RH at the coldest likely surface temperature.